• Home
  • About Us
    • Our History
    • Our Team
    • Experience and Projects
  • Shouldered Systems
    • Shouldered Pipe
      • ERW Pipe Galvanised
      • Spiral Welded Pipe Galvanised
      • Maxiflo Pipe ™ Shouldered Lite
    • Shouldered Couplings
      • 2 Bolt Couplings LSMG ™
      • 4 Bolt Couplings LSMG ™
      • SGI Quick Release Couplings LSMG ™
      • Replacement Rubber Gasket LSMG ™
      • No Lose Parts Couplings - Victaulic Style SC77
    • Shouldered Valves
      • Ball and Butterfly Valves
      • Check Valves
      • Gate Valves
      • Hydrant and Knifegate Valves
    • Shouldered Adaptors
      • Adaptors
      • Bends
      • Elbows
      • Tee Piece
      • Reducers
    • Shouldered Manifolds
      • Compressed Air
      • Firewater
      • Hydrant
      • Washdown
      • Wastewater
    • Shouldered Rings Accessories
    • Gas Measuring Dewatering - Drainage
  • Hose & Fittings
    • Mining FRAS
  • Piping Systems
    • Polyethylene Piping Systems
    • Ventilation Systems
      • Sizing
    • Piping System Design
    • Piping Installation
  • Civil
    • D.I.C.L.
    • Conduit
    • Storm and Sewer Projects
  • Contact
Shouldered Systems

Shouldered Pipe Systems

All A.C. Whalan & Co PTY LTD Shouldered Pipe is manufactured in an ISO 9002 accredited Mill from Mill test certificated Grade C350 strip then manufactured into CHS in accordance to AS:1163 & AS:1074.                                    
The welding of the Shouldered End Ring is conducted in house by the manufacturer and welded in accordance to AS:4041. The galvanizing is completed post end welding in accordance to AS/NZS 4680. The testing of the Shouldered product is conducted by accredited / certified testing facilities such as SGS or Bureau Veritas. With the Hydrostatic testing being conducted in accordance to AS:4037 and the tensile tests are conducted in accordance to AS:1391.                                    
                                    
As a result of the above minimum requirements, quality assurance, procedures, practises and testing we can confidently say & publish that the A.C Whalan & Co Hot Dipped Galvanised Shouldered Pipe has the following minimum strengths, tolerances & working pressures.    

MATERIAL STRENGTHS

  • Minimum Longitude Yield Strength 350 MPa
  • Minimum Transverse Yield Strength 289 MPa
  • Minimum Tensile Strength 430 MPa

DIMENSIONS - TOLERANCES - PRESSURES FOR STEEL SHOULDER PIPE

  • Weld – On steel shoulder rings provide an interference fit with the outside of the pipe ends and therefore must be a neat fit.
  • Pipe ends to which steel shoulder rings are to be fitted should be within the tolerances detailed under Shoulder Dimensions, refer to the below table.
  • The pipe ends should be measured with a circumferential tape ( or other effective averaging device ) to obtain these figures.
  • Pipe not within this tolerance must be sized for 50mm from the end.
  • Care is required when fitting shoulder rings to ensure that ring distortion does not occur.
  • It is important that the distance between the edge of the steel shoulder ring and the pipe end be accurately maintained. If this “Stand off” (refer to the below table) is exceeded, distortion will occur. A setting jig is recommended for holding & fixing.
  • The pipe ends & steel shoulder rings must be clean & free from rust, grease & paint before welding.
  • After welding, remove all splatter from the face & edge of the steel shoulder ring.
  • If after welding, pipe ends are found to be oval, they must be rounded to the standard dimensions & tolerances to fit the housings.

(Refer Shoulder dimensions)

SHOULDER DIMENSIONS
Outside
Dia
mm
Nominal
Pipe Size
mm
"D"
Dia
mm
"DS"
Dia
mm
TOLERANCE "L"
Dimension
mm
Plus            Minus
mm             mm
60.3 50 60.3 66.5 0.8 0.8 16
88.9 80 88.9 97 0.8 0.8 16
114.3 100 114.3 122 0.8 0.8 17.5
139.7 125 139.7 149 0.8 0.8 17.5
165.1 150 165.1 174.5 0.8 0.8 17.5
168.3 150 168.3 178 0.8 0.8 17.5
219.1 200 219.1 232 0.8 1.4 20.5

STAND OFF

  • 5mm for pipe 88.9mm outside diameter and below.
  • 6.5mm for pipe 114.3mm outside diameter up to and including 762mm outside diameter.

Stand Off

WORKING & TEST PRESSURES

Outside Diameter  mm Wall Thicknes mm Maximum Working Pressure Maximum Test Pressure Length Tolerance of Pipe Dimension Length


mpa mpa plus minus metre
60.3 3 11.6 19 50 0 6.5
114.3 2 5.6 8.8 50 0 6.5
165.1 2.5 4.8 8.8 50 0 6.5
219.1 3.2 4.4 6.5 50 0 6.5

  • The above test and working pressures only relate to internal pressures in straight pipe when the maximum working medium temperature is 50 degrees Celsius.
  • The maximum working pressure of a piping system is limited to the capabilities of the joining system. In the Shouldered Pipe Product this working pressure is limited to that of the Shouldered Couplings working pressure. Systems should therefore be designed with the couplings maximum working pressure in mind.

Give us a call !!!

Can't find the information you are looking for? Why not give us a call right now and one of our friendly team will offer you friendly service, or if your question is more technical we will have one of our Engineers or Technicians give you a call back at your convenience.

Here's a list of our sites direct phone numbers:
Singleton: Ph 02 6574 6811
Lithgow: Ph 02 6355 1001
Mackay: Ph 07 4942 5588
Gunnedah: Ph 02 6742 7135

contact ac whalan

Click Here!

To visit our Composites web site.

logo_green

Head Office

AC Whalan & Co. Pty Ltd
573 Putty Road,
Singleton NSW 2330
Tel: (02) 6574 6811
Fax: (02) 6574 6815

Email - Site Contact Addresses

Singleton Site: singleton@acwhalan.com.au
Lithgow Site: lithgow@acwhalan.com.au
Mackay Site: mackay@acwhalan.com.au
Gunnendah Site: gunnedah@acwhalan.com.au